SPECIFICATIONS |
MODEL
|
|
400AP
|
1000AP
|
Input
|
Capacity (VA) |
400
|
1000
|
|
Voltage |
110V or 220V ±25%
|
|
Frequency |
50 or 60 Hz ±10%
|
50 or 60 Hz ± 5%
|
Output
|
Voltage (on battery) |
Simulated Sinewave 110V or 220V ± 5%
|
|
Frequency (on battery) |
50 or 60 Hz ± 2%
|
|
Voltage Regulation
(AVR) |
AVR automatically increases output voltage 15% above input voltage if -9% to-25% of nominal
AVR automatically decreases output voltage 13% below input voltage if +9% to+25% of nominal
|
|
Transfer Time |
2/4 ms. including detection time
|
Battery
|
Type |
Sealed, Maintenance-free lead acid
|
|
Typical recharge time |
4 hours (to 90% of full capacity)
|
8 hours (to 90% of full capacity)
|
|
Protection |
Automatic self-test and discharge protection
|
|
Back-up Time |
10-30 minutes (depending on computer load)
|
Protection
& Filtering
|
Spike Protection |
320 joule, 2ms
|
|
Unit Input |
Fuse for overload & short circuit protection
|
|
Overload Protection |
Automatic shutdown if overload over 110% at 1 minute, and 130% at 3 sec.
|
|
Short Circuit Protection |
UPS output cut off immediately or input fuse protection
|
Alarms
|
Alarms |
Beeping sound for battery back up, battery low, overload status
|
Conformance
|
Surge |
Meet IEEE 587 standard
|
|
Safety |
EN-50091-1
|
|
EMC |
EN-50091-2
|
|
Protection Class |
IP20
|
Environment
|
Operating Temperature |
0-40 °C
|
|
Humidity |
0-95% non-condensing
|
|
Audible Noise at 1m |
< 40 dBA
|
< 48 dBA
|
Communication |
RS-232 Interface |
Bi-directional communication port
|
Physical
|
Net weight (kg) |
5.7
|
13.9
|
|
Shipping weight (kg) |
6.2
|
14.8
|
|
Dimension (mm) WxDxH |
100x330x137
|
125x390x200
|